De-Icing Solutions for California Facilities: What Works
January 28, 2026

Commercial building energy management is the routine of measuring what a building uses, finding where that energy is wasted and fixing the cheap problems before buying anything. For an office building in Silicon Valley, the order that works is to benchmark against similar buildings, match run times to how people actually use the space, tune the controls, and only then spend capital on lighting and equipment.
No honest article can promise your building a fixed percentage. What published studies can tell you is where savings tend to come from and what each step involves. The figures below are tied to the year and the scope of the study they come from.
Start by benchmarking, because you cannot manage a number you have not seen. ENERGY STAR Portfolio Manager is EPA's tool for this. ENERGY STAR describes it as a way to "measure and compare your building's energy to similar buildings, past consumption, or a reference performance level," and to identify underperforming buildings to target for efficiency improvements.
Two measures matter. Energy use intensity (EUI) is total energy consumed in one year divided by floor area, usually in kBtu per square foot. The 1 to 100 ENERGY STAR score then ranks the building against peers. On EPA's scoring page, a score of 50 represents median performance and a score of 75 or higher marks a top performer that may qualify for certification.
If your building is large, you may already be required to do this. California's AB 802 benchmarking program applies to buildings with more than 50,000 square feet of gross floor area, with reporting due every year by June 1. Even below that size, the same data tells you whether you are spending like an average building or like a wasteful one.
Heating, cooling and ventilation lead, with lighting next. The U.S. Energy Information Administration reports that in 2018 space heating was the largest single end use, about 32% of commercial building energy, with ventilation and lighting each at about 10%. Those are national figures for all commercial buildings, and the mix in a Bay Area office will differ with its climate and equipment. PG&E's own business rebate page puts HVAC at roughly 40 to 50 percent of a commercial building's energy.
Your own meter data is better than any average. Three patterns are worth looking for:
The first fixes are operational: schedules, setpoints and habits. They are also the ones most often skipped, because nobody owns them. A start time set years ago for a different tenant, a weekend schedule that never changed, or an override left on after a repair will quietly run for years.
A workable first pass looks like this:
This is also where the cleaning crew matters. A night janitorial team walks every floor, so it sees lights left on, doors propped open and equipment running in empty rooms. Writing a short lights-and-equipment checklist into the janitorial scope turns that visibility into a daily control, at no extra cost to the building.
Lighting is usually the safest capital project in an older building. The U.S. Department of Energy notes that a typical incandescent lamp lasts about 1,000 hours, while good-quality white LED products are expected to last 30,000 to 50,000 hours or longer. Less time spent replacing lamps is a maintenance saving that sits on top of the energy saving.
Controls are where more of the savings sit. A 2011 Lawrence Berkeley National Laboratory review of 240 savings estimates from 88 papers and case studies found best estimates of average savings of 24% for occupancy-based strategies, 28% for daylighting, 31% for personal tuning, 36% for institutional tuning and 38% for multiple approaches combined. These are averages across many buildings, so treat them as a reason to look, not a forecast for your floor.
Occupancy sensors earn their keep in conference rooms, storage rooms, restrooms and break rooms, where lights are most often left on. Daylight dimming suits perimeter offices near windows. Whatever you choose, have the controls commissioned after installation, because a sensor aimed at the wrong place or set too sensitive costs more in complaints than it saves.
Retro-commissioning is a systematic tune-up of an existing building's systems, and the research on it is some of the strongest in the field. A Lawrence Berkeley National Laboratory update that grew its database from 224 to 643 buildings reported 16% median whole-building energy savings in existing buildings, a median payback of 1.1 years and a median cost of $0.30 per square foot.
That study is from 2009 and costs have moved since, so use it for the shape of the result and not for budgeting. The point is that fixing what is already installed (sensors drifting out of calibration, schedules that no longer fit, valves stuck open) often pays back faster than new equipment.
Retro-commissioning needs a qualified engineer or commissioning provider. The facility team's role is to supply drawings, schedules and complaint history, give access to equipment rooms, and make sure the fixes stay in place after the engineer leaves.
Your rate plan decides which savings are worth chasing. PG&E's business time-of-use plans use a peak window of 4 to 9 p.m. every day, and energy used then costs more than energy used at other hours. Moving flexible loads, such as precooling the building before the peak, shifts use without reducing comfort.
Some plans also add a demand charge. On PG&E's time-of-use page, the charge is calculated using the 15-minute interval in each billing month when your business uses the most electricity, and the regular usage charges on such a plan can be roughly 30% lower than on a comparable plan without one. One brief spike can therefore set the charge for the whole month.
PG&E's advice for avoiding it is simple: do not run all your equipment at once. In a building, that means staggering chiller and fan startups, keeping a morning warm-up from landing on the same quarter hour as elevator and lighting load, and scheduling equipment tests off-peak. We cover this in more depth in our posts on peak demand charge management and on utility cost benchmarking and rate optimization.
Incentives can reduce the cost of lighting, HVAC controls and equipment, but the rules change often, so check before you buy. PG&E's business energy efficiency rebate page lists rebates for items such as demand control ventilation and advanced digital economizer controls, and says funding is limited and available on a first-come, first-served basis.
Confirm eligibility first, then plan the project around the program, not the other way around. Check whether the contractor needs specific qualifications, and keep the invoices, product data sheets and commissioning records together. Those documents are what a rebate application and a later audit will ask for.
What is a good ENERGY STAR score for an office building?
A score of 50 is the median for similar buildings, and EPA treats 75 or higher as top performance that can qualify for certification. The score adjusts for building characteristics and weather, so it compares like with like. A building below 50 usually has operational fixes available before it needs new equipment.
Do I have to benchmark my building in California?
If the building has more than 50,000 square feet of gross floor area, AB 802 requires annual energy reporting by June 1. Smaller buildings are not covered, but benchmarking them in Portfolio Manager is still the quickest way to see whether they use more than their peers.
What is the difference between a demand charge and a usage charge?
A usage charge bills the total energy you consume, while a demand charge bills your single highest 15-minute draw in the billing month. A building can use little energy overall and still pay a large demand charge if its loads all start together.
Where should a facility manager start?
Start with data: twelve months of bills, a Portfolio Manager account and a walk through the building at night and on a weekend. Fix schedules and setpoints first, since they cost little, then decide which capital projects to price based on what the data shows.
MAFM does not engineer energy systems, but our facility management team plans the work around them: building walkthroughs, schedule reviews, vendor coordination for commissioning and lighting projects, and a janitorial scope that supports your shutdown routines. Talk to us about facility management.
MAFM offers comprehensive facility management solutions tailored to your business needs.